Storage
Inverter Storage
The following requirements should be met if the inverter is not put into immediate use:
Do not unpack the inverter.
Keep the storage temperature at -40~60°C and the humidity at 5%~95% RH.
The inverter should be stored in a clean and dry place and be protected from dust and water vapor corrosion.
A maximum of six inverters can be stacked. To avoid personal injury or device damage, stack inverters with caution to prevent them from falling over.
During the storage period, check the inverter periodically. Replace any damaged packaging promptly.
The inverters stored for more than 2 years should be inspected and tested before being put into service.
Battery Storage
The following requirements should be met if the battery is not put into immediate use:
Place batteries according to the signs on the carton during storage.
Stack battery cartons in accordance with the stacking requirements printed on the external carton.
Store the battery out of reach of children and animals.
Store the battery in an area where there is minimal dust and dirt.
Handle batteries with care to avoid damage.
The requirements for the storage environment are as follows:
Ambient temperature: -10~55°C, recommended storage temperature: 15~30°C
Relative humidity: 15%~85%
Place batteries in a dry, clean, ventilated location free from dust.
Store batteries in a place that is away from corrosive organic solvents and gases.
Keep batteries away from direct sunlight.
Keep batteries at least 2 meters away from heat sources.
The batteries in storage must be disconnected from external devices and the indicators (if any) on the batteries should be off.
Warehoused batteries should be delivered based on the "first in, first out" stock control.
The warehouse keeper should collect battery storage information every month and report to the planning department. Batteries stored for more than 6 months should be assessed and charged periodically.
Capacity loss may occur if a lithium battery is stored for a long time. After a lithium battery is stored for 12 months in the recommended storage temperature, the irreversible capacity loss rate is 3%~10%. It is recommended that batteries not be stored for a long period. If the batteries need to be stored for more than 6 months, it is recommended to recharge the batteries to 65~75% of the SOC.
Transport
During transportation, please follow these guidelines:
Use the original packaging for transportation. If the original packaging is not available, place the product inside a suitable cardboard box with adequate protection and seal the carton.
Handle with care, choose the corresponding handling method according to the weight, and pay attention to safety. Mechanical aids should always be used in preference to lifting by hand.

Figure 4-1 Handling methods for batteries of different weights
Keep the packaging dry and away from potential sources of damage during transportation.
Secure the Product during transportation to prevent falling or mechanical impact.